Model | YT-2500L (linear), YT-2500R (rotary) |
Acting Type | Single or double acting |
Input Signal | 4 - 20mA DC |
Minimum Current Signal | 3.2mA (standard), 3.8mA (with HART) |
Impedance | Max. 460Ω at 20mA DC |
Supply Pressure | 1.4 - 7 kgf/cm² (0.14 - 0.7MPa) |
Stroke | 0 - 90° (YT-2500R), 10 - 150mm (YT-2500L) |
Air Connection | 1/4 G, 1/4 NPT, 1/4 PT |
Gauge Connection | 1/8 NPT, 1/8 PT |
Conduit Entry | NPT 1/2 (option for YT-2500L), 1/2 (standard for YT-2500R), PF 1/2 |
Protection Class | IP66 |
Ambient Temperature | Operating: -30 - 85°C; Explosion proof: -40 - 60°C (T5) / -40 - 40°C (T6) |
Linearity | ±0.5% F.S. |
Hysteresis | ±0.5% F.S. |
Sensitivity | ±0.2% F.S. |
Flow Capacity | 70 LPM |
Air Consumption (Idle) | Near zero (Sup = 1.4 kgf/cm²) |
Output Characteristic | Linear, quick open, equal percentage, user set (16 points) |
Vibration Resistance | 6g at 100Hz up to no resonance |
Humidity | 5 - 95% RH at 40°C |